6-LOAD 2-LOAD 8-LOAD
Figure 23 2-Load to 6 or 8-Load Conversion
Connect Input Feeds
Lug landings are 3/8-16 on 1” centers. See Figure 3 and Figure 4.
1.Input Feeds - Run and terminate input feed cables to the Load Shunt Bus of each load bus.
2. Input Feed Returns - Run and terminate input feed return cables to the Load Return Bus.
• Internal Return Bus - Figure 3 and Figure 4
• External Return Bus - Figure 10 and Figure 11
3.Torque hardware to 240 in-lb with 9/16” socket.
Connect Breaker/Fuse Loads
Lug Landings:
• Distribution Connections - 1/4-20 on 5/8” centers.
• Adapter Bus Kits – 3/8-16 on 1” centers.
See Figure 6, Figure 7, and Figure 9.
1. Two-Pole and Three-Pole Adapter Bus Kits - Install Two-Pole and Three-Pole Adapter Bus Kits
for each Breaker/Fuse Load fed by a Two-Pole and Three-Pole protector - .
• Secure the Mount Adapter Bus Kits to the associated connection landings with 1/4-20
hardware.
• Torque to 65 in-lb with 7/16” socket.