2. Breaker/Fuse Loads - Run and terminate Breaker/Fuse Load cables to the distribution
connection landings.
3. Input Feed Returns - Run and terminate input feed return cables to the Load Return Bus.
• Internal Return Bus - Figure 3 and Figure 4
• External Return Bus - Figure 10 and Figure 11
4. Torque all lug securing hardware:
• 1/4-20 hardware to 65 in-lb with 7/16” socket
• 3/8-16 hardware to 240 in-lb with 9/16” socket
Alarm Connections and ABS Power
At the top of the cabinet is a Customer Interface Board for connecting Output Alarms and Alarm
Battery Supply (ABS) to redundantly power the alarms and the VIM1C meter.
The VIM1C receives redundant power from panels 1 and 2 as well as an external ABS connection, so
the ABS connection is not mandatory for proper operation but some customers require its use.
A Return connection is required for operation of the meter and alarms. The Return connection on
the Customer Interface Board is factory wired when internal return buses are ordered, otherwise it
must be field wired to the external return bus.
• Contacts are rated for 60V, 1/2A.
• Maximum wire size to the terminal blocks is 12 AWG.
Alarm Outputs consist of single form-C contact for
• Power loss
• Current overload
• Fuse/breaker alarms
Note: there are two connection points for FAJ/CB but they are connected to the same form-C
contact.