3 - 4 WBPEEUI240766B0
Setup and Installation
Configuring Inputs
Configure the ASI module by setting the specifications in FCs
215 and 216 in the controller and setting the input jumpers on
both the ASI module and the termination unit. Refer to
Section 4 for more information on configuration and calibra-
tion.
Each input on the ASI module has a jumper block. The jumper
block has different ways it can be configured: millivolt, ther-
mocouple, RTD, voltage and current. Jumper block J1
matches channel one, jumper block J5 matches channel five,
jumper block J16 matches channel 16, etc. Each channel can
be configured independently. The ASI module can have any
number of inputs configured as resistance, low level voltage, or
high level voltage.
Figure 3-2. S1 Switch
Tabl e 3-1. S am ple A dd res s Switch Set ti ngs ( S1)
Address
Example
Switch Position
1,2
(Binary Value)
3
(32)
4
(16)
5
(8)
6
(4)
7
(2)
8
(1)
08 0 0 1 0 0 0
32 1 0 0 0 0 0
63 1 1 1 1 1 1
User setting
NOTES:
1. Switch positions 1 and 2 must be closed.
2. 0 = closed or on, 1 = open or off.
1 2 3 4 5 86 7
OPEN
MUST
REMAIN
CLOSED
I/O
ADDRESS
MSB LSB
T01800A
NOTE: OPEN POSITION = LOGIC 1