Loading...
Setup and Installation
WBPEEUI240766B0 3 - 5
The jumper settings are dictated by the firmware version and
the jumper block type. The firmware is available in different
versions. To verify the version, locate the information on the
U29 chip (Fig. 3-1). Depending on the module version, the
jumper blocks will have either six pins or four pins. To config-
ure the jumper blocks, refer to Table 3-2.
NOTE: Figure A-7 details the special configuration for the millivolt and RTD
input for a module with firmware version B.0 or higher and a four pin jumper
block.
Termination Un it Configura tion
An NTAI06 termination unit connects the field device wiring to
the Symphony system. The terminal blocks are located on the
termination unit. Set up the termination unit to accept the
analog field inputs sent to the IMASI13 module. Refer to
Appendix A for the termination unit information.
Tabl e 3-2. Jumper Bloc k Referen ce
Firmware Version
6-Pin Jumper Block
(J1 - J16)
4-Pin Jumper Block
(J1 - J16)
B.0 or higher Refer to Figure 3-4 Refer to Figure 3-3
and Figure A-7
A.6 or lower N/A Refer to Figure 3-3
Figure 3-3. Four Pin Jumper Block Configurations
Figure 3-4. Six Pin Jumper Block Configurations
±100 mV
TC
RTD
±10 VDC
4-20 mA
T04361A
mV/TC V/mA RTD
T04355A