6 - 2 WBPEEUI240766B0
Problem Reports
If the detailed module status read from the ASI module by
the controller indicates any error conditions.
If the channel status for any configured channel indicates
an error.
Table 6-1 contains the error types generated for each error.
Tabl e 6-1. I MA SI1 3 Error Ty pes
Module Problem Report Type 12
Error
Type
Error Description
Analog Input Module
Error
Corrective Actions
14 Calibration (0EH) problem
report (from FC 216)
Channel 1-16 disabled Remove IMASI13 and insert. If
error recurs, replace the IMASI13.
Calibration (0EH) problem
report (from FC 215)
Cold junction disabled
Calibration (0EH) problem
report (from FC 216)
Channel 1-16 not
calibrated
Calibration (0EH) problem
report (from FC 215)
Cold junction not
calibrated
7Configuration mismatch
problem report (from FC 216)
Channel not configured Verify that Specs S3 through S9 of
the indicated FC 216 are correct.
3Channel failure/out of range
(03H) problem report (from
FC 216)
Channel 1-16 out of
range error
Possible open input or signal is
out of range. Verify field wiring,
connections, sensor and module
seating.
Channel failure/out of range
(03H) problem report (from
FC 215)
Cold junction out of
range error
Channel failure/out of range
(03H) problem report (from
FC 216)
External cold junction
reference error
Ver ify quality of block defined for
Spec S3.
Channel failure/out of range
(03H) problem report (from
FC 216)
Channel 1-16 A/D
conversion error
Remove IMASI13 and insert. If
error recurs, replace the IMASI13.
Channel failure/out of range
(03H) problem report (from
FC 215)
Cold junction A/D con-
version error

Related product manuals