Wiring Connections and Cabling
WBPEEUI240766B0 3 - 7
the I/O expander bus for communication with the controller.
P1 and P2 connection require no additional wiring or cabling.
NOTE: A dipshunt on the backplane of the module mounting unit connects the
I/O expander bus between the ASI module and the controller. Locate the mod-
ule so the bus can connect to them or they will not communicate.
Cable Connections
The IMASI13 module uses one NTAI06 termination unit for
termination. The NTAI06 requires an NKAS01 or NKAS11
cable to connect to the IMASI13 module. The cables have a Y
configuration with two connectors on one end. Note the label-
ing of J2 and J3 to insure proper connection of the input sig-
nals. Figure 3-5 shows cable connections to the NTAI06
termination unit.
Figure 3-5. Cable Connections
T01066A
P1
P3
J3
P2
J2
P1
J1
P2
NKAS01/11
(NOTE 1)
TERMINATION UNIT
CABLE
NTAI06
CHANNELS 11-16
CHANNELS 1-10
IM AS I13
FIELD
WIRING
NOTE:
1. NKAS01 HAS PVC INSULATION (SPECIFY LENGTH UP TO 200 FT).
NKAS11 HAS NON-PVC INSULATION (SPECIFY LENGTH UP TO 200 FT).