LMT SERIES | MAGNETOSTRICTIVE LEVEL TRANSMITTER | OI/LMT100/200-EN REV.B
Menu: Device Setup (continued)
Menu/Parameter Value Range Description
Device Setup/Write Protect
Software WP On, Off Sets ability of user to edit parameters through software
Hardware WP Unlocked, Locked Sets ability of user to edit parameters through
mechanical switch on the top of the trasmitter housing
Device Setup/PV Setup
PV Unit • Unit length
- mm, cm, m, in, ft
• Unit volume
- Liters, Cubic meters, cubic inches, cubic feet, cubic
yards, gallons, Imperial gallons, bushels, barrels,
liquid barrels
• Unit flow
- Liters/second, liters/minute, liters/ hour, gallons/
second, gallons/minute, gallons/hour, gallons/day,
imperial gallons/ second, imperial gallons/minute,
imperial gallons/ hour, imperial gallons/day,
barrels/ second, barrels/minutes, barrels/ hour,
barrels/day, cubic meters/second, cubic meters/
minute, cubic meters/hour, cubic meters/day, cubic
feet/second, cubic feet/minute, cubic feet/hour,
cubic feet/day
Defines unit of measure for primary variable
PV LRV • Non linearized

• Linearized


value of the measuring span.
PV URV • Non linearized

• Linearized


value for the measuring span.
PV Damping Time  
Device Setup/Device
Variables/Level
Level Units mm, cm, m, in, ft Sets units for level output type
Lower Range • Non linearized

• Linearized

Upper Range • Non linearized

• Linearized

PV Offset 
Device Setup/Device
Variables/Interface
Lower Range • Non linearized

• Linearized

Damping Time 
Upper Range • Non linearized

• Linearized

Interface Offset 
Device Setup/Device
Variables/Temperature
C, F select temperature unit of measure
Lower Range 
Upper Range 
Temperature Offset 
Lower Temp Limit 
Upper Temp Limit 