Easy Setup
This menu allows the verification and the setting of parameters 
for the basic configuration of the LMT Series level transmitters. 
The menu-driven structure guides the user to the choice of 
interface language, the tag number configuration, the 
engineering units, the upper range value and the lower range 
value (URV and LRV) and the display visualization mode (the 
value that needs to be visualized on the HMI).
Device Setup
This menu allows the verification and the establishing of 
parameters related to the whole LMT Series of devices. The 
menu-driven structure includes enabling write-protection, 
setting process variables (unit, LRV and URV), selecting transfer 
functions (linearization type and low flow cutoff) and scaling 
output (unit according to the measurement and LRV / URV). The 
last selectable sub-menu allows the user to reset all the 
parameters to the default configuration.
Display
The Display menu allows the setup of different functions 
relevant to the display itself. The menu-driven structure guides 
the user through the choice of various functional aspects, such 
as the display language and contrast. Moreover, it is possible to 
choose, in detail, what displays on the screen: one or two lines 
with or without the bar graphs. Inside the menu, there is the 
possibility of setting a protection password (security) and the 
display scaling (linearization type, unit, LRV, URV). The display 
revision number is also available.
Process Alarm
This Alarm menu enables the parameterization of the alarm 
functions. The menu-driven structure guides the user through
the failsafe choices, such as the saturation limits and the fail 
level (upscale or downscale).
Calibrate
The Calibrate menu allows the local calibration of the 
instrument. The menu-driven structure allows the user to 
adjust sensor trimming (low or high) and the output settings 
(set to 4 or 20 mA).
Diagnostics
The Diagnostics menu is in place to allow the user to monitor 
diagnostic messages that relate to the pressure variable, output 
current, output percentage, scaled output, static and sensor 
pressure. The menu-driven structure guides the user through the 
loop test (set 4 and 20 mA and set the output value).
Device Info
The Device Info menu enables the user to retrieve all 
information about the device. The menu-driven structure 
shows the user the sensor type, the hardware and software 
revisions, the high and low sensor limits as well as the minimum 
applicable span.
Communication
The last section of the structured menu items, the 
Communication menu allows the user to change the 
communication tag and the MULTI-DROP mode with HART 
address numbers for the device. It is also where variables are 
assigned to HART addresses (PV, SV, TV, QV).