39
For example use the tank in 8.6.2.1-2, where the Diameter is
1000 mm, Length is 2500 mm, Input Unit is mm, Output type is
Volume, Output unit is liters
Point # 00 01 02 03 04 20
Input Value
<In> (mm)
Output
Value
<Out> (lit)
Using linearization tables
STEP 1:
Log in as an “Advanced user by pressing
STEP 2:
Press
to navigate to Device Setup menu
Press
to Select/Enter the Device Setup menu
STEP 3:
Press
to navigate to Linearization submenu
Press
to Select/Enter the Linearization menu
IMPORTANT NOTE
All parameters in the following section are edited the same
Configuring Setup
STEP 1:
Press
or to highlight setup
Press
to Select/enter into the Linearization setup menu
STEP 2:
Press
to Select/enter into the Table State menu
STEP 3:
Press
to edit the Table State
STEP 4:
Press
or to highlight an action
Press
to apply the highlighted action