50 M4M 20 NETWORK ANALYZER USER MANUAL
PROFIBUS (M4M 20 Profibus product version)
This section is available on M4M 20 Profibus with Profibus DP-V0 embedded communication.
→ Communication → Profibus
Menu Description
Address From 1 to 126.
If DHCP is disabled, the values of above configurations (IP address, subnet mask, gateway, TCP port) are
the default ones. In this case, it is possible to modify each of above configurations.
If DHCP is enabled, it is not needed to enter the above configurations as they are automatically set.
See Profibus communication manual for details on Profibus communication protocol and communication
map.
BACNET (M4M 20 Bacnet product version)
This section is available on M4M 20 Bacnet with BACnet/IP embedded communication.
→ Communication → BACnet
Parameter Range Default value Comments
DHCP enabled/disabled disabled
IP address
0.0.0.0-
255.255.255.255
192.168.1.12
This address must create valid
Network prefix and Host address
with combination of subnet mask,
accordingly to IPv4 subnetting.
Additionally some ranges according to
IANA organization are excluded from
valid values: (127.0.0.0-127.0.0.255),
(224.0.0.0-239.255.255.255) and
255.255.255.255.
Subnet mask
128.0.0.0-
255.255.255.254
255.255.255.0
It must be valid according to IPv4
subnetting.
Gateway
0.0.0.0-
255.255.255.255
192.168.1.1
This address follows the same
restrictions as IP address of device.
UDP port 0-65535 47808
Device instance 0-4194302 228
This ID must be unique across BACnet
network.
BBMD enabled/disabled disabled
BBMD IP address
0.0.0.0-
255.255.255.255
0.0.0.0
BBMD UDP port 0-65535 47808
BBMD TTL 0-65535 0
Ekip Connect mode enabled/disabled disabled
Ekip Connect mode item shall be used only for FW upgrade via Ekip Connect desktop. When Ekip Connect
mode is enabled, the device reboots and waits for FW upgrade. At the end of the firmware upgrade
operation the device will reboot with the updated firmware. Once the device has rebooted, ensure that
Ekip connect mode parameter is disabled.
If DHCP is disabled, the values of above configurations are the default ones. In this case, it is possible to
modify each of above configurations.
If DHCP is enabled, it is not needed to enter the above configurations as they are automatically set.
See Bacnet communication manual for details on Bacnet communication protocol and communication map.