M4M 20 NETWORK ANALYZER USER MANUAL
7
2.Packaging contents
Packaging contents
1 Network analyzer M4M 20 or M4M 20-M (MID)
2 Installation manual
3 Calibration certificate
4 Installation accessories (removable terminals, fixing clips)
5 M4M 20-M (MID): Sealable terminal block
The number and type of removable terminals in the package varies according to the different versions.
Please refer to below table to check the removable terminals included in each package.
Product
Name
Current input
terminal (6
poles)
Voltage input
terminal (4
poles)
Auxiliary supply
terminal (2
poles)
Digital outputs
terminal (3
poles)
Programmable
I/O terminal (3
poles)
Analogue output
terminal (3
poles)
RS485 terminal
(3 poles)
M4M 20 X X X X - - -
M4M 20
MODBUS
X X X X - - X
M4M 20-M
MODBUS
X X X X - - X
M4M 20
ETHERNET
X X X X - - -
M4M 20-M
ETHERNET
X X X X - - -
M4M 20
PROFIBUS
X X X X - - -
M4M 20 I/O X X X X X X X
M4M 20
BACNET
X X X X - - -
M4M 20
ROGOWSKI
- X X X - - X
Please notice that terminals for current input on M4M 20 Rogowski are pre-wired on ABB’s R4M
Rogowski coils
M4M Calibration Certificate
This Calibration Certificate may not be reproduced, in whole or in part,
without written permission of ABB
Test Conditions Test Description Accuracy
Test
Result
No.
V1
[V]
V2
[V]
V3
[V]
I1
[A]
I2
[A]
I3
[A]
PF R esults Limit
#1 230 230 230 6 6 6 1
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#2 230 230 230 0,9 0,9 0,9 1
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#3 230 230 230 0,15 0,15 0,15 1
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#4 230 230 230 6 6 6 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#5 230 230 230 0,9 0,9 0,9 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#6 230 230 230 0,15 0,15 0,15 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#7 230 230 230 1,5 1,5 1,5 1
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#8 230 230 230 0,2 0,2 0,2 1
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#9 230 230 230 1,5 1,5 1,5 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#10 230 230 230 0,2 0,2 0,2 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#11 230 230 230 6 6 6 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#12 230 230 230 0,9 0,9 0,9 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#13 230 230 230 0,15 0,15 0,15 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#14 58 58 58 6 6 6 1
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#15 58 58 58 6 6 6 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#16 230 230 230 6 - 6 1
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#17 230 230 230 0,9 - 0,9 1
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#18 230 230 230 0,15 - 0,15 1
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#19 230 230 230 6 - 6 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#20 230 230 230 0,9 - 0,9 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
#21 230 230 230 0,15 - 0,15 0,5 ind.
Verification –
Active energy (Import)
-0,01% ±0,5% Passed
Contact us
ABB S.p.A.
Electrification Business
Viale dell’Industria, 18
20010 Vittuone (MI) Italy
https://new.abb.com/low-voltage
Graphs
Data Reading
Configuration
Network analyzer
INSTALLATION MANUAL
M4M 20
2CSG445030D0201 July 2019
Warning! Installation by person
with electrotechnical expertise
only.
Warnung! Installation nur durch
elektrotechnische Fachkraft.
Avvertenza! Fare installare solo da
un elettricista qualificato.
1.Packaging Content
Network analyzer M4M 20
Installation manual
Calibration certificate
2 mounting clips
Removable terminals for wiring
2.Mounting
2.1.Assembly
2.2.Wiring Diagram
For current measurement, please
notice that it is needed to fasten
the screw-type terminal to the
device with the two screws.
3.Symbol instruction
Button Function
Shortcut to Home/
Favorite/Notifications
pages.
BACK
Return to the previous
page.
ENTER
Confirm the selection.
Increase or decrease the
value. Keeping pressed will
increase the speed of the
number variation.
Move cursor up or down.
Move cursor to the left or to
the right.
Confirm selection with
ENTER
CT ratio L1 L2 L3
Select the current transformer ratio among
the default ones or enter it manually.
In case of manual entry, enter the value
of the primary with + or - and select the
secondary (1A or 5A).
Enter the voltage transformer ratio (both
primary and secondary) manually with + or -.
Manual
40/5 A
50/5 A
60/5 A
CT ratio L1 L2 L3
-
+
MORE
Finalize the installation through
removable terminals.
Default password is 00000. At
first use, the password shall be
defined. In order to disable the
password, please enter 00000.
4.Access to device
Graphs
Data Reading
Configuration
Access to device is done through the five
buttons under the screen.
The home page is divided in 3 sections:
Sections Description
Graphs
Graphical representation
of the main parameters.
Data Reading
Values of the main
parameters.
Configuration
Setup of the device.
Unit
Language
Installation
CT ratio
In case of direct insertion,
400/400V value shall be used.
→ Installation → VT ratio
CT ratio L1 L2 L3
Confirm selection with
ENTER
Confirm selection with
ENTER
Confirm selection with
ENTER
3Ph/4W/3CT
3Ph/3W/3CT
3Ph/3W/2CT
3Ph/3W/1CT
Parameter Description
3Ph/4W/3CT 3-phase 4-wire + 3CTs
3Ph/4W/1CT 3-phase 4-wire + 1CT
3Ph/3W/1CT 3-phase 3-wire + 1CT
3Ph/3W/3CT 3-phase 3-wire + 3CTs
3Ph/3W/2CT 3-phase 3-wire + 2CTs
2Ph/3W/2CT 2-phase 3-wire + 2CTs
1Ph/2W/1CT 1-phase 2-wire + 1CT
Select the type of network among the
following ones:
Installation
Type of network
3-phase 4-wire network with 3CTs
3-phase 4-wire network with 1CT
3-phase 3-wire network with 1CT
3-phase 3-wire network with 3CTs
3-phase 3-wire network with 2CTs
2-phase 3-wire network with 2CTs
1-phase 2-wire network with 1CT
5.First Commissioning
To start to use the analyzer it is mandatory
to configure the basic setting (password,
language, type of network, CT ratio and VT
ratio).
5.1.Setting password
The password is composed by 5 numerical
characters. In order to select each numerical
character, it is necessary to use + or - and
confirm every selection with ENTER.
5.2.Setting language
5.3.Type of network
5.4.Current Transformer ratio
5.5.Voltage Transformer ratio
Select the desired language for the
display among the ones available.
QR Code for online
User Manual.
© Copyright 2019 ABB S.p.A. All rights
reserved. Specification subject to change
without notice.

1
2
3
4
1
4
5
4
2 3