86  FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D   
 
… 8  Operation 
 
… Parameter descriptions 
 
Menu / parameter  Description 
Device Setup / ...Transmitter / ...Feature Settings 
Backwards Comp.  Indicator as to whether the backward compatibility function has been activated. 
Backwards Comp. Code  Set the device-specific code for activating the function. To use this function subsequently, contact the ABB service team or 
sales organization. 
After entering the code, restart the device (e.g. using the parameter ‘Device Reset’ or by briefly switching off the power 
supply). 
Verifying Capab.   Indicator as to whether the verification function has been activated. 
Verifying Capab.Code  Set the device-specific code for activating the verification function. To use this function subsequently, contact the ABB 
service team or sales organization. 
After entering the code, restart the device (e.g. using the parameter ‘Device Reset’ or by briefly switching off the power 
supply). 
Batchmode  Indicator as to whether the filling function has been activated. 
Batchmode Code  Set the device-specific code to activate the filling function. To use this function subsequently, contact the ABB service team 
or sales organization. 
After entering the code, restart the device (e.g. using the parameter ‘Device Reset’ or by briefly switching off the power 
supply). 
Expert Diagn.  Indicator as to whether advanced diagnosis functions such as gas bubble or conductivity have been activated. 
Expert Diagn. Code  Set the device-specific code for activating the advanced diagnosis function. To use this function subsequently, contact the 
ABB service team or sales organization. 
After entering the code, restart the device (e.g. using the parameter ‘Device Reset’ or by briefly switching off the power 
supply). 
SIL Comp.  Indicator as to whether the SIL function is active. 
SIL Comp. Code  Set the device-specific code for activating the SIL function. To use this function subsequently, contact the ABB service team 
or sales organization. 
After entering the code, restart the device (e.g. using the parameter ‘Device Reset' or by briefly switching off the power 
supply). 
 
Device Setup / ...System Zero 
Manual Adjust  Sets the value for zero point adjustment in % of Q
max
DN 
Manual adjustment: −50 to +50 mm/s 
Auto Adjust  Starts the automatic zero point balancing using  . Automatic zero point balancing takes approx. 60 seconds. 
Note 
Prior to starting the zero point adjustment, make sure that: 
•  There is no flow through the sensor (close all valves, shut-off devices etc.) 
•  The sensor must be filled completely with measuring medium for measurement.