102  FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D   
 
… 8  Operation 
… Parameter descriptions 
 
Menu / parameter  Description 
Diagnostics / ...Diagnosis Values 
All values in this menu are for informational and service purposes only. 
Inhouse Temperature  Display of temperature value within the transmitter housing. 
Inhouse Temp MaxPeak 
Inhouse Temp MinPeak 
Driver Current  Display of the drive current of the sensor coil. 
Signal Region on ADC  Display of the measuring signal within the A / D converter input. 
(-100 % to +100 %) 
Coil DAC Preset  Display of the D / A converter for coil drive. 
DC Feedback DAC   D / A converter feedback value. 
ADC Errors  A / D converter error 
Device Restart Count  Number of device restarts (boots). 
 
Diagnostics / ......Simulation Mode 
Simulation Switch  Manual simulation of measured values. After selecting the value to be simulated, a corresponding parameter is displayed in 
the menu ‘Diagnostics / ......Simulation Mode’. The simulation value can be set here. 
The output values correspond to the simulated flowrate entered. 
The ‘Configuration’ information is displayed in the lower line of the display. 
Only one measured value / output can be selected for simulation. 
After power-up / restart of the device, the simulation is switched off. 
 
Off 
Qm Massflow [unit] 
Qm Massflow [%] 
Qv Volumeflow [unit] 
Qv Volumeflow [%] 
Conductivity[µS/cm] 
Curr.Out 31/32 
Curr.Out V1/V2 
Curr.Out V3/V4 
Dig.Out 41/42 State 
Dig.Out 41/42 Freq. 
Dig.Out 41/42 Pulse 
Dig.Out 51/52 State 
Dig.Out 51/52 Pulse 
Dig.Out V1/V2 State 
Dig.Out V3/V4 State 
Dig.In V1/V2 State 
Dig.In V3/V4 State 
Hart Frequency