FEP630, FEH630 ELECTROMAGNETIC FLOWMETER  |  OI/FEP630/FEH630-EN REV. D  57 
 
Menu   
Easy Setup 
 
Exit  Select
 
5. Use   /   to select ‘Easy Setup’. 
6. Confirm the selection with  . 
 
Easy Setup   
Language 
 
Language
Next  Edit
 
7. Use   to call up the edit mode. 
8. Use   /   to select the desired language. 
9. Confirm the selection with  . 
 
Easy Setup   
Unit Volumeflow Q
 
 
l/s
Next  Edit
 
10.Use   to call up the edit mode. 
11. Use   /   to select the desired unit for the volume flow 
rate. 
12. Confirm the selection with  . 
 
 
Easy Setup   
Qv Max 1 
 
25.000 l/s
Next  Edit
 
13. Use   to call up the edit mode. 
14. Use   /   to set the desired upper range value. 
15. Confirm the selection with  . 
 
The device is factory calibrated to the flow range end value 
Q
max
DN, unless other customer information is available. The 
ideal upper range values are those which correspond to a flow 
velocity of 2 to 3 m/s (0.2 to 0.3 × Q
max
DN) 
The adjustable upper range values are listed in the table at 
Measuring range table on page 60. 
 
Easy Setup   
Unit Vol. Totalizer 
 
l/s
Next  Edit
 
16. Use   to call up the edit mode. 
17. Use   /   to select the desired unit for the volume 
totalizer. 
18. Confirm the selection with  . 
 
Easy Setup   
Pulses per Unit 
 
10.000/m³
Next  Edit
 
19. Use   to call up the edit mode. 
20.Use   /   to select the desired pulse per unit for the 
pulse output. 
21. Confirm the selection with  .