21
FEM630 | ELECTROMAGNETIC FLOWMETER  |  OI/FEM630-EN REV. A
5     ...Installation
Installing the transmitter in the remote 
mount design
When selecting a location for the transmitter, consider the 
following points:
•  Observe the information concerning maximum ambient 
temperature and IP rating on the name plate
•  The location must be mostly free from vibration. 
•  The location must not be exposed to direct sunlight. If 
necessary provide a sun screen on site.
•  Do not up-scale the maximum signal cable length 
between the transmitter and the sensor.
1  Drill mounting holes at mounting location.
2  Attach transmitter securely to the mounting location 
using suited fasteners for the base material.
G11567
205 (8.07)
2x45 = 90
(2x1.77 = 3.54)
262 (10.31)
71 (2.8)
71 (2.8)
Ø 7 (0.28)
1
Hole pattern for mounting holes
Hole pattern for mounting holes
1
1
Figure 19  Mounting dimensions dual-compartment housing
Figure 20  Mounting dimensions single-compartment housing