Table 30: X120 AIM binary input signals
Name Type Description
X120-Input 1 BOOLEAN Connectors 1-2c
X120-Input 2 BOOLEAN Connectors 3-2c
X120-Input 3 BOOLEAN Connectors 4-2c
X120-Input 4 BOOLEAN Connectors 5-6
Table 31: X120 AIM binary input settings
Parameter Values (Range) Unit Step Default Description
Input 1 filter time 5...1000 ms 5 Connectors 1-2c
Input 2 filter time 5...1000 ms 5 Connectors 3-2c
Input 3 filter time 5...1000 ms 5 Connectors 4-2c
Input 4 filter time 5...1000 ms 5 Connectors 5-6
Input 1 inversion 0=False
1=True
0=False Connectors 1-2c
Input 2 inversion 0=False
1=True
0=False Connectors 3-2c
Input 3 inversion 0=False
1=True
0=False Connectors 4-2c
Input 4 inversion 0=False
1=True
0=False Connectors 5-6
Table 32: X130 BIO binary output signals
Name
Type Default Description
X130-SO1 BOOLEAN 0=False Connectors
10c-11no-12nc
X130-SO2 BOOLEAN 0=False Connectors
13c-14no-15nc
X130-SO3 BOOLEAN 0=False Connectors
16c-17no-18nc
Table 33: X130 BIO binary input signals
Name
Type Description
X130-Input 1 BOOLEAN Connectors 1-2c
X130-Input 2 BOOLEAN Connectors 3-2c
X130-Input 3 BOOLEAN Connectors 4-5c
X130-Input 4 BOOLEAN Connectors 6-5c
X130-Input 5 BOOLEAN Connectors 7-8c
X130-Input 6 BOOLEAN Connectors 9-8c
1YHT530004D05 D Section 3