Table 34: X130 BIO binary input settings
Parameter Values (Range) Unit Step Default Description
Input 1 filter time 5...1000 ms 5 Connectors 1-2c
Input 2 filter time 5...1000 ms 5 Connectors 3-2c
Input 3 filter time 5...1000 ms 5 Connectors 4-5c
Input 4 filter time 5...1000 ms 5 Connectors 6-5c
Input 5 filter time 5...1000 ms 5 Connectors 7-8c
Input 6 filter time 5...1000 ms 5 Connectors 9-8c
Input 1 inversion 0=False
1=True
0=False Connectors 1-2c
Input 2 inversion 0=False
1=True
0=False Connectors 3-2c
Input 3 inversion 0=False
1=True
0=False Connectors 4-5c
Input 4 inversion 0=False
1=True
0=False Connectors 6-5c
Input 5 inversion 0=False
1=True
0=False Connectors 7-8c
Input 6 inversion 0=False
1=True
0=False Connectors 9-8c
Table 35: X130 AIM binary input signals
Name
Type Description
X130-Input 1 BOOLEAN Connectors 1-2
X130-Input 2 BOOLEAN Connectors 3-4
X130-Input 3 BOOLEAN Connectors 5-6
X130-Input 4 BOOLEAN Connectors 7-8
Table 36: X130 AIM binary input settings
Parameter
Values (Range) Unit Step Default Description
Input 1 filter time 5...1000 ms 5 Connectors 1-2
Input 2 filter time 5...1000 ms 5 Connectors 3-4
Input 3 filter time 5...1000 ms 5 Connectors 5-6
Input 4 filter time 5...1000 ms 5 Connectors 7-8
Input 1 inversion 0=False
1=True
0=False Connectors 1-2
Input 2 inversion 0=False
1=True
0=False Connectors 3-4
Input 3 inversion 0=False
1=True
0=False Connectors 5-6
Input 4 inversion 0=False
1=True
0=False Connectors 7-8
Section 3 1YHT530004D05 D
Basic functions
58 615 series
Technical Manual