Description DNP point
address
Event class UR enable Value range Comment
DI2 41 1 1 0/1 1 = activated
DI3 42 1 1 0/1 1 = activated
DI4 43 1 1 0/1 1 = activated
DI5 44 1 1 0/1 1 = activated
Disturbance recorder 45 1 1 0/1 1 = triggered
0 = cleared
HMI Setting password 46 1 1 0/1 1 = opened
0 = closed
IRF 47 1 1 0/1 1 = activated
Warning 48 1 1 0/1 1 = activated
SPA event overflow 49 1 1 0/1 1 = activated
HMI Communication password 50 1 1 0/1 1 = opened
0 = closed
Table 5.1.16.2.-2 Analog data
Description DNP point
address
Event class UR enable Deadband Value range Internal
scaling
factor (ix = 0)
Phase current I
L1
xI
n
02110...5000 100
Phase current I
L2
xI
n
12110...5000 100
Phase current I
L3
xI
n
22110...5000 100
Earth-fault current x I
n
32110...20000 10
Phase unbalance 42110...100 100
Thermal level 52110...106 100
One-minute demand value 62110...5000 100
Demand value during the specified
time range
72110...5000 100
Maximum one-minute demand
value during the specified time
range
82110...5000 100
Table 5.1.16.2.-3 Counters
Description DNP point
address
Event class UR enable Deadband Value range
Number of starts of stage I> 0 3 1 1 0...999
Number of starts of stage I>> 1 3 1 1 0...999
Number of starts of stage I>>> 2 3 1 1 0...999
Number of starts of stage I
0
> 3 3 1 1 0...999
Number of starts of stage I
0
>> 4 3 1 1 0...999
Number of starts of stage ΔI> 5 3 1 1 0...999
Number of trips of stage I> 6 3 1 1 0...65535
Number of trips of stage I>> 7 3 1 1 0...65535
Number of trips of stage I>>> 8 3 1 1 0...65535
Number of trips of other stages 9 3 1 1 0...65535
Number of AR shots (shot 1) initiated by
the trip signal from stage I>>
10 3 1 1 0...255
102
REF 610REF 610
Feeder Protection Relay
Technical Reference Manual
1MRS755310