Event reason
Event code
Configuration set 1
Configuration set 2
Function type
Information number
GI
Relative time
Type identification
Open CB Command/Reset 3E13/
3E14
X X 169 127 - - 1
Close CB Command/Reset 3E15/
3E16
X X 169 128 - - 1
CB Reclosing Failed/Reset 3E17/
3E18
X X 169 163 - - 1
CB Reclosing inhibited/Reset 3E19/
3E20
X X 169 162 - - 1
AR Cancelled/Reset 3E21/
3E22
X X 169 130 - - 1
Table 5.1.14.-2 Information mapping of configuration set 1 and 2
Measurand
Normalize factor
Rated value
Configuration set 1
Configuration set 2
Function type
Information number
Type identification
Current I
L1
2.4 I
n
X X 135 140 9
Current I
L2
2.4 I
n
XX
Current I
L3
2.4 I
n
XX
Current I
0
2.4 I
n
XX
5.1.15. Modbus remote communication protocol
The master/slave protocol Modbus was first introduced by Modicon Inc. and is
widely accepted as a communication standard for industrial device controllers and
PLCs. For the protocol definition, refer to Section 1.4. Product documentation.
The implementation of the Modbus protocol in the relay supports both the RTU and
the ASCII link mode. Both the link mode and the line setting parameters are user-
configurable. The character codings of the link modes follow the protocol
definition. The RTU character format is presented in Table 5.1.15.-1 and the ASCII
character format in Table 5.1.15.-2:
84
REF 610REF 610
Feeder Protection Relay
Technical Reference Manual
1MRS755310