REGISTER Data description
Number of
starts
The number of times each protection stage, I>, I>>, I>>>, ΔI, I
0
> and I
0
>>, has
started, counting up to 999.
Number of
trips
*
The number of times each protection stage, I>, I>>, I>>>, has tripped. When
the counters reach their maximum values (65535), it will roll over.
*
The number of times protection stages, I
0
> and I
0
>>, θ> and ARC has
tripped and external trips. When the counter reaches its maximum value
(65535), it will roll over.
Number of
AR shots
*
Number of AR shots (shot 1) initiated by the trip signal from stage I>>,
counting up to 255
*
Number of AR shots (shot 1) initiated by the digital input signal, counting up
to 255
*
Number of AR shots (shot 1) initiated by the start or trip signal from stage I> ,
counting up to 255
*
Number of AR shots (shot 1) initiated by the pickup or trip signal from stage
I
0
>, counting up to 255
*
Number of AR shots (shot 2) initiated by the trip signal from stage I>>,
counting up to 255
*
Number of AR shots (shot 2) initiated by the digital input signal, counting up
to 255
*
Number of AR shots (shot 2) initiated by the start or trip signal from stage I>,
counting up to 255
*
Number of AR shots (shot 2) initiated by the start or trip signal from stage I
0
>,
counting up to 255
*
Number of AR shots (shot 3) initiated by the trip signal from stage I>>,
counting up to 255
*
Number of AR shots (shot 3) initiated by the digital input signal, counting up
to 255
*
Number of AR shots (shot 3) initiated by the start or trip signal from stage I>,
counting up to 255
*
Number of AR shots (shot 3) initiated by the start or trip signal from stage I
0
>,
counting up to 255
5.1.13. Communication ports
The relay is provided with an optical communication port (infrared) on the front
panel. Rear communication is optional and requires a communication module,
which can be provided with either a plastic fibre-optic, combined fibre-optic (plastic
and glass) or RS-485 connection. The relay is connected to an automation system
via the rear connection. The optional rear communication module allows the use of
either the SPA bus, IEC 60870-5-103 or Modbus communication protocol.
For connection to the DNP 3.0 communication system, the relay can be provided
with an optional DNP 3.0 rear communication module with RS-485 connection. For
further information on optional rear communication module connections, refer to
Section 5.2.3. Serial communication connections.