EasyManua.ls Logo

ABB REF 610 - 6 Application Examples; Auto-Reclose Function; Fast Tripping and Initiation of Shot 1 Using Two Protection Stages

ABB REF 610
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
153
6. Application examples
6.1. Auto-reclose function
6.1.1. Fast tripping and initiation of shot 1 using two protection stages
In several applications, such as fuse-saving applications involving down-stream
fuses, tripping and initiation of shot 1 should be fast (instantaneous or short-time
delayed) and of shot 2 and 3, and definite tripping time delayed. In this example,
two overcurrent stages are used, I> and I>>. Stage I>> is given an instantaneous
characteristic and Stage I> a time delay. By setting SG2/2 to 1 and SG2/7 to 1, Stage
I>> will be blocked by the AR function during shot 2 and 3.
I>>
I>
SG2/2=1
SG2/7=1
01
t>> t>
t>
t>
Trip
Trip
Block I>>
Close CB
CB closed
CB open
Shot 1
Shot 2 Shot 3
Definite Trip
I>> Trip
I> Trip
Block I>> at
Shot 1, 2 and 3
Block I>>
I> Trip
Block I>>
I> Trip
Block I>>
Open CB
Open CB
A040360
Fig. 6.1.1.-1 Fast initiation of shot 1 using one fast and one delayed stage
In case of a short-circuit in the network, stage I>> will trip the circuit breaker and
initiate shot 1. At the time of shot initiation, the blocking of stage I>> will be
activated. If the network fault is not cleared, stage I> will trip the circuit breaker and
continue the auto-reclose sequence to shot 2, shot 3 and finally definite tripping.
As the set start value of stage I> in this example is higher than that of stage I>>, as
sometimes is the case, it is possible that the current will not exceed the set start value
of stage I> while the blocking of stage I>> is active. This will lead to a pumping
effect when the AR function is reset (the blocking of stage I>> included), i.e. the AR
sequence will start over and over again.
To avoid such a pumping effect, a cutout time is used. The cutout time, like the
reclaim time, will start when the set dead time elapses and the AR function issues a
reclosing command to the circuit breaker. By setting the cutout time to be shorter
Feeder Protection Relay
Technical Reference Manual
REF 610REF 610
1MRS755310

Table of Contents

Other manuals for ABB REF 610

Related product manuals