8. Check lists
Table 8.-1 Setting group 1
Variable Group/
Channel
1 (R, W,
P)
Setting
range
Default
setting
Custo-
mer ’s
setting
Start value of stage I> 1S1 0.30...5.0 x I
n
0.30 x I
n
Operate time of stage I> 1S2 0.05...300 s 0.05 s
Time/current characteristic for stage I> 1S3 0...9 0
Time multiplier k 1S4 0.05...1.00 0.05
Time multiplier n 1S5 1.0...15.0 1.0
Resetting time of stage I> 1S6 0.05...2.50 s 0.05 s
Start value of stage I>> 1S7 0.50...35.0 x
I
n
0.50 x I
n
Operate time of stage I>> 1S8 0.04...300 s 0.04 s
Start value of stage I>>> 1S9 0.50...35.0 x
I
n
0.50 x I
n
Operate time of stage I>>> 1S10 0.04...30.0 s 0.04 s
Start value of stage I
0
> 1S11 1.0...100% I
n
1.0% I
n
Operate time of stage I
0
> 1S12 0.05...300 s 0.05 s
Time/current characteristic for stage I
0
> 1S13 0...9 0
Time multiplier k
0
1S14 0.05...1.00 0.05
Time multiplier n
0
1S15 1.0…15.0 1.0
Resetting time of stage I
0
> 1S16 0.05...2.50 s 0.05 s
Start value of stage I
0
>> 1S17 5.0...800% I
n
5.0% I
n
Operate time of stage I
0
>> 1S18 0.05...300 s 0.05 s
Start value of stage ΔI> 1S19 10...100% 100 %
Operate time of stage ΔI> 1S20 1...300 s 60 s
Full load current 1S21 0.30...1.50 x
I
n
0.30 x I
n
Time constant of stage θ> 1S22 1...200 min 1 min
Alarm level of stage θ> 1S23 50...100%
θ
t
>
95% θ
t
>
Operate time of CBFP 1S24 0.10...60.0 s 0.10 s
Number of AR shots 1S25 0 = AR is not
in use
1 = shot 1
2 = shot 1
and 2
3 = shot 1, 2
and 3
0
Current limit ArcI> of stage ARC 1S26 0.50...35.0 x
I
n
2.50 x I
n
Current limit ArcI
0
> of stage ARC 1S27 5.0...800% I
n
20% I
n
Checksum, SGF 1 1S61 0...255 0
Checksum, SGF 2 1S62 0...127 0
Checksum, SGF 3 1S63 0...127 120
Checksum, SGF 4 1S64 0...63 0
Feeder Protection Relay
Technical Reference Manual
REF 610REF 610
1MRS755310