Variable Group/
Channel
1 (R, W,
P)
Setting
range
Default
setting
Custo-
mer ’s
setting
Checksum, SGF 5 1S65 0...255 0
Checksum, SGB 1 1S71 0...1048575 0
Checksum, SGB 2 1S72 0...1048575 0
Checksum, SGB 3 1S73 0...1048575 0
Checksum, SGB 4 1S74 0...1048575 0
Checksum, SGB 5 1S75 0...1048575 0
Checksum, SGR 1 1S81 0...8388607 2108074
Checksum, SGR 2 1S82 0...8388607 2108074
Checksum, SGR 3 1S83 0...8388607 2108074
Checksum, SGR 4 1S84 0...8388607 5461
Checksum, SGR 5 1S85 0...8388607 5461
Checksum, SGR 6 1S86 0...8388607 0
Checksum, SGR 7 1S87 0...8388607 0
Checksum, SGR 8 1S88 0...8388607 0
Checksum, SGL 1 1S91 0...8388607 0
Checksum, SGL 2 1S92 0...8388607 0
Checksum, SGL 3 1S93 0...8388607 0
Checksum, SGL 4 1S94 0...8388607 0
Checksum, SGL 5 1S95 0...8388607 0
Checksum, SGL 6 1S96 0...8388607 0
Checksum, SGL 7 1S97 0...8388607 0
Checksum, SGL 8 1S98 0...8388607 0
Table 8.-2 Setting group 2
Variable Group/
Channel 2
(R, W, P)
Setting range Default
setting
Custo-
mer ’s
setting
Start value of stage I> 2S1 0.30...5.0 x I
n
0.30 x I
n
Operate time of stage I> 2S2 0.05...300 s 0.05 s
Time/current characteristic for
stage I>
2S3 0...9 0
Time multiplier k 2S4 0.05...1.00 0.05
Time multiplier n 2S5 1.0...15.0 1.0
Resetting time of stage I> 2S6 0.05...2.50 s 0.05 s
Start value of stage I>> 2S7 0.50...35.0 x I
n
0.50 x I
n
Operate time of stage I>> 2S8 0.04...300 s 0.04 s
Start value of stage I>>> 2S9 0.50...35.0 x I
n
0.50 x I
n
Operate time of stage I>>> 2S10 0.04...30.0 s 0.04 s
Start value of stage I
0
> 2S11 1.0...100% I
n
1.0% I
n
Operate time of stage I
0
> 2S12 0.05...300 s 0.05 s
Time/current characteristic for
stage I
0
>
2S13 0...9 0
Time multiplier k
0
2S14 0.05...1.00 0.05
164
REF 610REF 610
Feeder Protection Relay
Technical Reference Manual
1MRS755310