105
Other value: 999 (Counters 0...5) and 255
(Counters 10...21)
Point-by-point list attached
Sends Multi-Fragment Responses
Yes No
Table 5.1.16.3.-1 Supported function codes
Code Function Description Supported
Transfer Function Codes
0 Confirm Message fragment confirmation
No response
Yes
1 Read Request objects from outstation
Respond with requested objects
Yes
2 Write Store specified objects to outstation
Respond with status of operation
Yes
Control Function Codes
3 Select Select output point of outstation
Respond with status of control point
No
4 Operate Set previously selected output
Respond with status of control point
No
5 Direct operate Set output directly
Respond with status of control point
No
6 Direct operate NO ACK Set output directly
No response
No
Freeze Function Codes
7 Immediate Freeze Copy specified objects to freeze buffer
Respond with status of operation
Yes
8 Immediate Freeze NO ACK Copy specified objects to freeze buffer
No response
Yes
9 Freeze and Clear Copy specified objects to freeze buffer and clear objects
Respond with status of operation
Yes
a)
10 Freeze and Clear NO ACK Copy specified objects to freeze buffer and clear objects
No response
Yes
a)
11 Freeze with time Copy specified objects to freeze buffer at specified time
Respond with status of operation
No
12 Freeze with time NO ACK Copy specified objects to freeze buffer at specified time
No response
No
Application Control Function Codes
13 Cold Restart Perform desired reset sequence
Respond with a time object
Yes
14 Warm Restart Perform desired partial reset operation
Respond with a time object
Yes
15 Initialize Data to Defaults Initialize the specified data to default
Respond with status of operation
No
16 Initialize Application Set the specified application ready to be run
Respond with status of operation
No
17 Start Application Start the specified application to run
Respond with status of operation
Yes
18 Stop Application Stop the specified application to run
Respond with status of operation
Yes
Configuration Function Codes
Feeder Protection Relay
Technical Reference Manual
REF 610REF 610
1MRS755310