Recorded data Parameter (R) Value
64=I
L1
>>
128=I
0
>>
256=I
L3
>>>
512=I
L2
>>>
1024=I
L1
>>>
2048=ΔI>
4096=θ>
8192=external trip
16384=AR
32768=trip of stage ARC (local)
65536=trip of stage ARC (remote)
Trip indication
code
V2 0 =
1=start of stage I>
2=trip of stage I>
3=start of stage I>>
4=trip of stage I>>
5=start of stage I>>>
6=trip of stage I>>>
7=start of stage I
0
>
8=trip of stage I
0
>
9=start of stage I
0
>>
10=trip of stage I
0
>>
11=start of stage ΔI>
12=trip of stage ΔI>
13=alarm of stage θ>
14=trip of stage θ>
15=external trip
16=definite trip alarm
17=CB reclosing failed
18=AR shot due
19=AR lockout
20=trip of stage ARC
21=CBFP
Number of starts of
stage I>
V3 0...999
Number of starts of
stage I>>
V4 0...999
Number of starts of
stage I>>>
V5 0...999
Number of starts of
stage I0>
V6 0...999
Number of starts of
stage I0>>
V7 0...999