Recorded data Event (R) Value
n Channel 1 n-1 Channel 2 n-2 Channel 3 n-3 Channel 4 n-4 Channel 5
Trip number of AR
sequence
1V19 2V19 3V19 4V19 5V19 0...255
Start duration of stage
ARC (local)
1V20 2V20 3V20 4V20 5V20 0/100%
Start duration of stage
ARC (remote)
1V21 2V21 3V21 4V21 5V21 0/100%
Time stamp of the
recorded data, date
1V22 2V22 3V22 4V22 5V22 YY-MM-DD
Time stamp of the
recorded data, time
1V23 2V23 3V23 4V23 5V23 HH.MM;
SS.sss
a)
If the thermal protection has been set out of operation (SGF3/5), dashes will be shown on the LCD and “999” when the parameter is read via
the SPA bus.
Disturbance recorder
Table 5.1.17.-5 Parameters for the disturbance recorder
Description Parameter (channel 0) R, W Value
Remote triggering M1
a)
W1
Clear recorder memory M2 W 1
Sampling rate M15
b)
R, W 800/960 Hz
400/480 Hz
50/60 Hz
Station identification/unit number M18 R, W 0...9999
Rated frequency M19 R 50 or 60 Hz
Name of the feeder M20 R, W Max 16 characters
Digital channel texts M40...M47 R -
Analog channel texts M60...M63 R -
Analog channel conversion factor and unit
for I
L1
,I
L2
and I
L3
M80
c)d)
R, W Factor 0...65535, unit (A,
kA), e.g. 10,kA
M81 and R
M82 R
Analog channel conversion factor and unit
for the earth-fault current
M83
c)
R, W Factor 0...65535, unit (A,
kA), e.g. 10,kA
Internal trigger signals' checksum V236 R, W 0...16383
Internal trigger signal's edge V237 R, W 0...16383
Checksum of internal signal storing mask V238
b)
R, W 0...16383
Post-triggering recording length V240 R, W 0...100%
External trigger signal's checksum V241 R, W 0...31