121
Table 5.1.17.-7 Disturbance recorder external triggering and storing
Event Weighting factor Default value of
triggering mask,
V241
Default value of
triggering edge,
V242
a)
Default value of
storing mask,
V243
DI11000
DI22000
DI34000
DI48000
DI5 16 0 0 0
Σ 000
a)
0 = rising edge; 1 = falling edge.
Table 5.1.17.-8 Control parameters
Description Parameter R, W, P Value
Reading of the event buffer L R Time, channel number and event code
Re-reading of the event buffer B R Time, channel number and event code
Reading of relay state data C R 0 = Normal state
1 = The relay has been subject to an
automatic reset
2 = Overflow of the event buffer
3 = Both 1 and 2
Resetting of relay state data C W 0 = Reset E50 and E51
1 = Reset only E50
2 = Reset only E51
4 = Reset all events including E51 except for
E50
Time reading and setting T R, W SS.sss
Date and time reading and setting D R, W YY-MM-DD HH.MM;SS.sss
Type designation of the relay F R REF 610
Unlatching output contacts V101 W 1 = Unlatch
Clearing indications and memorized values and
unlatching contacts (master reset)
V102 W 1 = Clear and unlatch
Resetting of trip lockout V103 W 1 = Reset
Rated frequency V104 R, W (P) 50 or 60 Hz
Time setting range for demand values in
minutes
V105 R, W 0...999 min
Non-volatile memory settings V106 R, W 0...31
Time setting for disabling new trip indications on
the LCD
V108 R, W (P) 0...999 min
Testing the self-supervision V109 W (P) 1 = Self-supervision output contact is
activated and the READY indicator LED
starts to blink
0 = Normal operation
LED test for start and trip indicators V110 W (P) 0 = Start and trip LEDs off
1 = Trip LED on, start LED off
2 = Start LED on, trip LED off
3 = Start and trip LEDs on
LED test for programmable LEDs V111 W (P) 0...255
Trip-circuit supervision V113 R, W 0 = Not in use
1 = In use
Feeder Protection Relay
Technical Reference Manual
REF 610REF 610
1MRS755310