123
Table footnotes from previous page
c)
If the optional DNP 3.0 module has been installed, the DNP 3.0 communication protocol is automatically selected.
d)
If the optional communication module is not installed, a warning of a faulty communication module appears on the LCD together with the fault
code.
The measured currents can be read with parameters I1...I4, the calculated phase
discontinuity value with parameter I5, the status of light detection with parameter
I6, the CB position with parameter I7 and the status of the digital inputs with
parameters I8...I12.
Table 5.1.17.-9 Input signals
Description Channel Parameter (R) Value
Current measured on phase I
L1
0 I1 0...50 x I
n
Current measured on phase I
L2
0 I2 0...50 x I
n
Current measured on phase I
L3
0 I3 0...50 x I
n
Measured earth-fault current 0 I4 0...2000% I
n
Calculated phase discontinuity
value
0 I5 0...100%
Light detected (arc) 0 I6 0/1
CB position 0,3 I7 0 = undefined
1 = closed
2 = open
3 = undefined
DI1 status 0,2 I8 0/1
a)
DI2 status 0,2 I9 0/1
a)
DI3 status 0,2 I10 0/1
a)
DI4 status 0,2 I11 0/1
a)
DI5 status 0,2 I12 0/1
a)
a)
When the value is 1, the digital input is energized.
Each protection stage has its internal output signal. These signals can be read with
parameters O1...O26 and the recorded functions with parameters O61...O86. The
state of the output contacts can be read or changed with parameters O41...O49 and
the recorded functions read with parameters O101...O109.
Table 5.1.17.-10 Output signals
Status of the
protection
stages
Channel State of stage
(R)
Recorded
functions (R)
Value
Start of stage I> 0,1 O1 O61 0/1
Trip of stage 0,1 O2 O62 0/1
Start of stage
I>>
0,1 O3 O63 0/1
Trip of stage
stage I>>
0,1 O4 O64 0/1
Start of stage
I>>>
0,1 O5 O65 0/1
Trip of stage
I>>>
0,1 O6 O66 0/1 ;
Start of stage I
0
> 0,1 O7 O67 0/1
Feeder Protection Relay
Technical Reference Manual
REF 610REF 610
1MRS755310