Switching between setting groups via a digital input has a higher
priority than via the HMI or with the parameter V150.
The setting values can be altered via the HMI or with a PC provided with Relay
Setting Tool.
Before the relay is connected to a system it must be assured that the relay has been
given the correct settings. If there is any doubt, the setting values should be read
with the relay trip circuits disconnected or tested with current injection; refer to
Section 8. Check lists for additional information.
Table 5.1.4.10.-1 Setting values
Setting Description Setting range Default setting
I>/I
n
Start value of stage I> 0.30...5.00 x I
n
0.30 x I
n
t> Operate time of stage I> 0.05...300 s 0.05 s
IDMT I> Time/current characteristic for stage
I>
0...9 0
k Time multiplier k 0.05...1.00 0.05
n Time multiplier n 1.0...15.0 1.0
t
r
> Resetting time of stage I> 0.05...2.50 s 0.05 s
I>>/I
n
Start value of stage I>> 0.50...35.0 x I
n
0.50 x I
n
t>> Operate time of stage I>> 0.04...300 s 0.04 s
I>>>/I
n
Start value of stage I>>> 0.50...35.0 x I
n
0.50 x I
n
t>>> Operate time of stage I>>> 0.04...30.0 s 0.04 s
I
0
>/I
n
Start value of stage I
0
> 1.0...100% I
n
1.0% I
n
t
0
> Operate time of stage I
0
> 0.05...300 s 0.05 s
IDMT I
0
> Time/current characteristic for stage
I
0
>
0...9 0
k
0
Time multiplier k
0
0.05...1.00 0.05
n
0
Time multiplier n
0
1.0…15.0 1.0
t
0r>
Resetting time of stage I
0
> 0.05...2.50 s 0.05 s
I
0
>>/I
n
Start value of stage I0>> 5.0...800% I
n
5.0% I
n
t
0
>> Operate time of stage I
0
> 0.05...300 s 0.05 s
ΔI> Start value of stage ΔI> 10...100% 100 %
t
Δ
> Operate time of stage ΔI> 1...300 s 60 s
I
θ
Full load current 0.30...1.50 x I
n
0.30 x I
n
T Time constant of stage θ> 1...200 min 1 min
θ
a
> Alarm level of stage θ> 50...100% θ
t
> 95% θ
t
>
CBFP Operate time of CBFP 0.10...60.0 s 0.10 s
0→1 Number of AR shots 0 = AR is not in use
1 = shot 1
2 = shot 1 and 2
3 = shot 1, 2 and 3
0
ArcI> Current limit ArcI> of stage ARC 0.50...35.0 x I
n
2.50 x I
n
ArcI
0
> Current limit ArcI
0
> of stage ARC 5.0...800% I
n
20.0% I
n
56
REF 610REF 610
Feeder Protection Relay
Technical Reference Manual
1MRS755310