Table 5.1.4.10.-2 SGF1
Switch Function Default setting
SGF1/1 Selection of the latching feature for PO1 0
SGF1/2 Selection of the latching feature for PO2 0
SGF1/3 Selection of the latching feature for PO3
*
When the switch is in position 0 and the measuring signal which caused the trip falls below
the set start value, the output contact returns to its initial state.
*
When the switch is in position 1, the output contact remains active although the measuring
signal which caused the trip falls below the set start value.
A latched output contact can be unlatched either via the HMI, a digital input or the serial bus.
0
SGF1/4 Minimum pulse length for SO1 and SO2 and optional SO3, SO4 and SO5
*
0 = 80 ms
*
1 = 40 ms
0
SGF1/5 Minimum pulse length for PO1, PO2 and PO3
*
0 = 80 ms
*
1 = 40 ms
The latching feature being selected for PO1, PO2 and PO3 overrides this
function.
0
SGF1/6
CBFP
*
0 = CBFP is not in use
*
1 = the signal to PO1 starts a timer which generates a delayed signal to PO2, provided that
the fault is not cleared before the CBFP operate time has elapsed
0
SGF1/7 Trip lockout function
*
0 = the trip lockout function is not in use. PO3 works as a normal power output relay.
*
1 = the trip lockout function is in use. PO3 is dedicated to this function.
0
SGF1/8 External fault warning
*
When the switch is in position 1, the warning signal from the trip-circuit supervision or
generated in case of continuous light on light sensor inputs is routed to SO2.
0
ΣSGF1 0
Table 5.1.4.10.-3 SGF2
Switch Function Default setting
SGF2/1 Operation mode of the start indication of stage I>
a)
0
SGF2/2 Operation mode of the start indication of stage I>> 0
SGF2/3 Operation mode of the start indication of stage I>>>
a)
0
SGF2/4 Operation mode of the start indication of stage I
0
>0
SGF2/5 Operation mode of the start indication of stage I
0
>>
a)
0
SGF2/6 Operation mode of the start indication of stage ΔI> 0
SGF2/7 Operation mode of the alarm indication of stage θ>
a)
*
0 = the start indication is automatically cleared after the fault has disappeared
*
1 = latching. The start indication remains active although the fault has disappeared.
0
ΣSGF2 0
a)
When the switch is on, the phase(s) that caused the start are shown on LCD.
58
REF 610REF 610
Feeder Protection Relay
Technical Reference Manual
1MRS755310