Switch Function Default setting
SGF5/7 Selection of the latching feature for programmable LED7 0
SGF5/8
Selection of the latching feature for programmable LED8
*
When the switch is in position 0 and the signal routed to the LED is reset, the programmable
LED is cleared.
*
When the switch is in position 1, the programmable LED remains lit although the signal
routed to the LED is reset.
A latched programmable LED can be cleared either via the HMI, a digital input or the serial bus.
0
ΣSGF5 0
SGB1...SGB5
The DI1 signal is routed to the functions below with the switches of switchgroup
SGB1, the DI2 signal with those of SGB2, and so forth.
Table 5.1.4.10.-7 SGB1...SGB5
Switch Function Default setting
SGB1...5/1
*
0 = indications are not cleared by the digital input signal
*
1 = indications are cleared by the digital input signal
0
SGB1...5/2
*
0 = indications are not cleared and latched output contacts are not unlatched by the digital
input signal
*
1 = indications are cleared and latched output contacts are unlatched by the digital input
signal
0
SGB1...5/3
*
0 = indications and memorized values are not cleared and latched output contacts are not
unlatched by the digital input signal
*
1 = indications and memorized values are cleared and latched output contacts are unlatched
by the digital input signal
0
SGB1...5/4 Switching between setting groups 1 and 2 by using the digital input
*
0 = the setting group cannot be changed using the digital input
*
1 = the setting group is changed by using the digital input. When the digital input is energized,
setting group 2 is activated, if not, setting group 1 is activated.
When SGB1...5/4 is set to 1, it is important that the switch has the same setting
in both setting groups.
0
SGB1...5/5 Time synchronization by the digital input signal 0
SGB1...5/6 External tripping by the digital input signal 0
SGB1...5/7 External triggering of the CBFP by the digital input signal 0
SGB1...5/8 External triggering of the trip lockout by the digital input signal 0
SGB1...5/9 External arc signalling by the digital input signal 0
SGB1...5/10 Resetting of the trip lockout by the digital input signal 0
SGB1...5/11 Blocking of tripping of stage I> by the digital input signal 0
SGB1...5/12 Blocking of tripping of stage I>> by the digital input signal 0
SGB1...5/13 Blocking of tripping of stage I
0
> by the digital input signal 0
SGB1...5/14 Blocking of tripping of stage I
0
>> by the digital input signal 0
SGB1...5/15 Blocking of tripping of stage ΔI> by the digital input signal 0
SGB1...5/16 External AR inhibition by the digital input signal 0
SGB1...5/17 External inhibition of CB reclosing by the digital input signal 0
60