Table 5.1.14.-1 Information mapping of configuration set 1 and 2
Event reason
Event code
Configuration set 1
Configuration set 2
Function type
Information number
GI
Relative time
Type identification
Disturbance recorder Triggered/Cleared 0E31/
0E32
X X 178 100 - - 1
HMI Setting password Opened/Closed 0E33/
0E34
X X 178 101 - - 1
HMI Communication password Opened/Closed 0E35/
0E36
X X 178 102 - - 1
I> Start/Reset 1E1/
1E2
X X 160 84 X 1E1 2
I> Trip/Reset 1E3/
1E4
X X 160 90 - 1E1 2
I>> Start/Reset 1E5/
1E6
X X 162 94 X 1E5 2
I>> Trip/Reset 1E7/
1E8
X X 160 91 - 1E5 2
I>>> Start/Reset 1E9/
1E10
X X 162 96 X 1E9 2
I>>> Trip/Reset 1E11/
1E12
X X 162 98 - 1E9 2
I
0
> Start/Reset 1E13/
1E14
X X 160 67 X 1E13 2
I
0
> Trip/Reset 1E15/
1E16
X X 160 92 - 1E13 2
I
0
>> Start/Reset 1E17/
1E18
X X 162 95 X 1E17 2
I
0
>> Trip/Reset 1E19/
1E20
X X 160 93 - 1E17 2
ΔI> Start/Reset 1E21/
1E22
X X 173 84 X 1E21 2
ΔI> Trip/Reset 1E23/
1E24
X X 173 90 - 1E21 2
θ> Start/Reset 1E25/
1E26
X X 184 84 X 1E25 2
θ> Alarm/Reset 1E27/
1E28
X X 184 11 X - 1
θ> Trip/Reset 1E29/
1E30
X X 184 90 - 1E25 2
ARC (light and current) Trip/Reset 1E31/
1E32
X X 100 90 - 1E31 2
ARC (DI and current) Trip/Reset 1E33/
1E34
X X 100 50 - 1E33 2
Arc light signal output Activated/Reset 1E35/
1E36
X X 100 20 - - 1