93
Table 5.1.15.1.-7 Mapping of Modbus data: analog data
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Phase current I
L1
xI
n
404 0...5000 0...50 x
Phase current I
L2
xI
n
405 0...5000
Phase current I
L3
xI
n
406 0...5000 0...50 x
Earth-fault current x I
n
407 0...20000 0...2000% I
n
Phase unbalance ΔI 408 0...100 0...100%
Table 5.1.15.1.-8 Mapping of Modbus data: digital data
Description HR/IR address (.bit) DI/Coil bit
address
Writeable Value
range
Comment
Start signal from stage I> 409.00 1 0/1 1 = activated
Start signal from stage I> CD 409.01 2
Trip signal from stage I> 409.02 3 0/1 1 = activated
Trip signal from stage I> CD 409.03 4
Start signal from stage I>> 409.04 5 0/1 1 = activated
Start signal from stage I>> CD 409.05 6
Trip signal from stage I>> 409.06 7 0/1 1 = activated
Trip signal from stage I>> CD 409.07 8
Start signal from stage I>>> 409.08 9 0/1 1 = activated
Start signal from stage I>>> CD 409.09 10
Trip signal from stage I>>> 409.10 11 0/1 1 = activated
Trip signal from stage I>>> CD 409.11 12
Start signal from stage I
0
> 409.12 13 0/1 1 = activated
Start signal from stage I
0
> CD 409.13 14
Trip signal from stage I
0
> 409.14 15 0/1 1 = activated
Trip signal from stage I
0
> CD 409.15 16
Start signal from stage I
0
>> 410.00 17 0/1 1 = activated
Start signal from stage I
0
>> CD 410.01 18
Trip signal from stage I
0
>> 410.02 19 0/1 1 = activated
Trip signal from stage I
0
>> CD 410.03 20
Start signal from stage ΔI> 410.04 21 0/1 1 = activated
Start signal from stage ΔI> CD 410.05 22
Trip signal from stage ΔI> 410.06 23 0/1 1 = activated
Trip signal from stage ΔI> CD 410.07 24
Start signal from stage θ> 410.08 25 0/1 1 = activated
Start signal from stage θ> CD 410.09 26
Alarm signal from stage θ> 410.10 27 0/1 1 = activated
Alarm signal from stage θ> CD 410.11 28
Trip signal from stage θ> 410.12 29 0/1 1 = activated
Trip signal from stage θ> CD 410.13 30
Trip signal from stage ARC (light and
current)
410.14 31 0/1 1 = activated
Trip signal from stage ARC (light and
current) CD
410.15 32
Feeder Protection Relay
Technical Reference Manual
REF 610REF 610
1MRS755310

Table of Contents