Test point Reach Set value Comments
11 X 0.8 x X1
set
Exact –0.5 x R1
set
x
tan(ArgNegRes=30°)
R –0.37 x X1
set
12 X 0.5 x X1
set
R 0.5 x R1
set
13 X 0 Only used when
OperationLdCmp
setting is 0 (Off)
R 0.5 x RFPP
Table 12 is used in conjunction with Figure 31.
X1+XN
X
R (Ohm/loop)
50%
80%
1
2
3
4
5
6
7
8
9
10
11
80% of RLdFw
40% of RLdFw
RFPE
12
13
c
b
=
A
r
g
L
D
alt. 80% of
RFPE (Load
encroachment)
120°
20°
a
IEC05000369-3-en.vsd
IEC05000369 V3 EN
Figure 32: Distance protection characteristic with test points for phase-to-earth
measurements
Table 13 is used in conjunction with Figure 32.
Table 13: Test points for phase-to-earth L3-E (Ohm/Loop)
Test point
Reach Value Comments
1 X (2 x X1
set
+X0
set
)/3
R 0
2 X (2 x X1
set
+ X0
set
)/3
R 2 x R1
set
+ R0
set
)/3
3 X 0.8 x (2 x X1
set
+ X0
set
)/3
R 0.8 x (2 x R1
set
+ R0
set
)/3 +RFPE
set
4 X 0.5 x (2 x X1
set
+ R0
set
)/3
R 0.5 x (2 x R1
set
+R0
set
)/3 + RFPE
set
Table continues on next page
Section 12 1MRK502053-UEN B
Testing functionality by secondary injection
112 Generator protection REG670 2.0 IEC
Commissioning manual