Figure 34: Distance protection characteristic with test points for phase-to-earth
measurements
Table 13 is used in conjunction with figure 32.
Table 15: Test points for phase-to-earth L3-E (Ohm/Loop)
Test point
Reach Value Comments
1 X (2 x X1
set
+X0
set
)/3
R 0
2 X (2 x X1
set
+ X0
set
)/3
R 2 x R1
set
+ R0
set
)/3
3 X 0.8 x (2 x X1
set
+ X0
set
)/3
R 0.8 x (2 x R1
set
+ R0
set
)/3 +RFPE
set
4 X 0.5 x (2 x X1
set
+ R0
set
)/3
R 0.5 x (2 x R1
set
+R0
set
)/3 + RFPE
set
5
X 0.85 x RFPE
set
x tan(ArgLdset) ArgLd = angle for the maximal load
transfer
R 0.85 x RFPE
6 X RLdFwset x tan(ArgLdSet)
R RLdFw
set
7 X 0
R RLdFw
set
8 X –02143 x RLdFw
set
Exact: 0.8 x RFPE x tan (ArgDir=20°)
R 0.8 x RLdFw
set
9 X –0.8 x RLdFw
set
x tan(ArgDir=20°)
R 0.8 x RLdFw
set
Table continues on next page
1MRK502053-UEN B Section 12
Testing functionality by secondary injection
Generator protection REG670 2.0 IEC 117
Commissioning manual