91
Event function (EV) Chapter 7
Logic
T_SUPR11 0.000-60.000
Step: 0.001
0.000 s Suppression time for event input 11 and 12.
Can only be set using the CAP 540 configu-
ration tool.
T_SUPR13 0.000-60.000
Step: 0.001
0.000 s Suppression time for event input 13 and 14.
Can only be set using the CAP 540 configu-
ration tool.
T_SUPR15 0.000-60.000
Step: 0.001
0.000 s Suppression time for event input 15 and 16.
Can only be set using the CAP 540 configu-
ration tool.
NAMEy 0-16 EVnn-INP-
UTy
Char User name of signal connected to input y,
y=01-16. String length up to 19 characters.
Can only be set using the CAP 540 configu-
ration tool.
PrColnn 0-7 0 - Protocol for event block nn (nn=01-06). 0:
Not used, 1: SPA, 2: LON, 3: SPA+LON, 4:
IEC, 5: IEC+SPA, 6: IEC+LON, 7:
IEC+LON+SPA. Range valid only for blocks
EV01-EV06. Can only be set from CAP 540
configuration tool.
PrCoInn 0-3 0 - Protocol for event block nn (nn=07-44). 0:
Not used, 1: SPA, 2: LON, 3: SPA+LON
Range valid only for blocks EV07-EV44. Can
only be set from CAP 540 configuration tool.
INTERVAL 0 - 60
Step: 1
0 s Cyclic sending of data. Can only be set from
CAP 540 configuration tool.
BOUND 0, 1 0 - Event connected to other terminals on the
network, 0: not connected, 1: connected.
Can only be set from CAP 540 configuration
tool.
FuncTEVnn 0-255
Step: 1
0 - Function type for event block nn (nn=01-06),
used for IEC protocol communication. Only
present in blocks EV01-EV06.
InfoNoy 0-255
Step: 1
0 - Information number for event input y,
y=01-16. Used for IEC protocol communica-
tion. Only present in blocks EV01-EV06.
EventMasky No events,
OnSet, OnRe-
set,
OnChange,
Double Ind.,
Double Ind.
with midpos.
No events - Event mask for input y, y=01-16. Can only be
set from PST.
Parameter Range Default Unit Description