Serial communication Chapter 9
Data communication
2.5.4 Function block
2.5.5 Input and output signals
Table 138: Input signals for the IEC (ICOM-) function block
Path in local HMI: ServiceReport/Functions/IEC103Command
Table 139: Output signals for the IEC (ICOM-) function block
2.5.6 Setting parameters
Table 140: Setting parameters for the IEC (ICOM-) function block
xx00000225.vsd
ICOM-
IEC870-5-103
FUNCTYPE
OPFNTYPE
ARBLOCK
ZCOMBLK
BLKFNBLK
LEDRS
SETG1
SETG2
SETG3
SETG4
BLKINFO
Signal Description
FUNCTYPE Main function type for terminal
OPFNTYPE Main function type operation for terminal
Signal Description
ARBLOCK Command used for switching autorecloser on/off.
ZCOMBLK Command used for switching teleprotection on/off.
BLKFNBLK Command used for switching protection on/off.
LEDRS Command used for resetting the LEDs.
SETG1 Command used for activation of setting group 1.
SETG2 Command used for activation of setting group 2.
SETG3 Command used for activation of setting group 3.
SETG4 Command used for activation of setting group 4.
BLKINFO Output activated when all information sent to master is blocked.
Parameter Range Default Unit Description
FuncType 0-255 0 - Main function type for terminal
Set from CAP 540
OpFnType Off, On Off - Main function type operation for terminal
Set from CAP 540