Configurable logic blocks (CL1) Chapter 3
Common functions
Table 43: Input signals for the TIMERLONG (TLnn-) function block
Path in local HMI: ServiceReport/Functions/TimerLong
Table 44: Output signals for the TIMERLONG (TLnn-) function block
6.6.1 Setting parameters
Table 45: Setting parameters for the TimerLong (TLnn-) function
6.7 Pulse timer function block (TP)
The pulse function can be used, for example, for pulse extensions or limiting of operation of out-
puts. The pulse timer TP has a settable length.
Table 46: Input signals for the TP (TPnn-) function block
Path in local HMI: ServiceReport/Functions/Pulsen
Signal Description
INPUT Input to long timer
T Time value. See setting parameters
Signal Description
OFF Output from long timer, drop-out delayed
ON Output from long timer, pick-up delayed
xx00000162.vsd
TL01-
TIMERLONG
INPUT
T
OFF
ON
Parameter Range Default Unit Description
T 0.0-90000.0
Step:0.1
0.0 s Delay for TLnn function. Can only be set
from CAP configuration tool.
Signal Description
INPUT Input to pulse timer
T Pulse length. See setting parameters
xx00000163.vsd
TP01-
PULSE
INPUT
T
OUT