Tripping logic (TR) Chapter 7
Logic
Table 99: Setting parameters for the trip logic TR (TR---) function
1.5 Technical data
Table 100: TR - Tripping logic
Parameter Range Default Unit Description
Operation Off / On Off - Operating mode for TR function
tTripMin 0.000-60.000
Step. 0.001
0.150 s Minimum duration of trip time
Parameter Value Accuracy
Setting for the minimum trip
pulse length, tTripMin
0.000 - 60.000 s in steps of 1 ms ± 0.5% ± 10 ms