Configurable logic blocks (CL1) Chapter 3
Common functions
Table 59: Input signals for the GT (GTnn-) function block
Path in local HMI: ServiceReport/Functions/ControlGates1/FuncOutputs
Table 60: Output signals for the GT (GTnn-) function block
6.12.1 Setting parameters
Path in local HMI: Settings/Functions/Groupn/ContrGates1/Gaten
Table 61: Setting parameters for the GT (GTnn-) function
6.13 Settable timer function block (TS)
The function block TS timer has outputs for delayed input signal at drop-out and at pick-up. The
timer has a settable time delay. It also has an Operation setting On, Off that controls the opera-
tion of the timer.
Table 62: Input signals for the TS (TSnn-) function block
Path in local HMI: ServiceReport/Functions/TimerSet1/FuncOutputs
Signal Description
INPUT Input to gate
Signal Description
Out Output from gate
xx00000380.vsd
GT01-
GT
INPUT OUT
Parameter Range Default Unit Description
Operation Off/On Off - Operating mode for GTn function
Signal Description
INPUT Input to timer
xx00000381.vsd
TS01-
TS
INPUT ON
OFF