90
Event function (EV) Chapter 7
Logic
2.4 Input and output signals
Table 101: Input signals for the EVENT (EVnn-) function block
2.5 Setting parameters
Table 102: Setting parameters for the EVENT (EVnn-) function
Signal Description
INPUTy Event input y, y=1-16
NAMEy User name of signal connected to input y, y=01-16. String length up to
19 characters.
T_SUPR01 Suppression time for event inputs 1and 2
T_SUPR03 Suppression time for event inputs 3 and 4
T_SUPR05 Suppression time for event inputs 5 and 6
T_SUPR07 Suppression time for event inputs 7 and 8
T_SUPR09 Suppression time for event inputs 9 and 10
T_SUPR11 Suppression time for event inputs 11 and 12
T_SUPR13 Suppression time for event inputs 13 and 14
T_SUPR15 Suppression time for event inputs 15 and 16
PrColnn Protocol for event block nn (nn=01-06). 0: Not used, 1: SPA, 2: LON,
3: SPA+LON, 4: IEC, 5: IEC+SPA, 6: IEC+LON, 7: IEC+LON+SPA.
Protocol for event block nn (nn=07-44). 0: Not used, 1: SPA, 2: LON,
3: SPA+LON
INTERVAL Time setting for cyclic sending of data
BOUND Input signals connected to other terminals on the network, 0: not con-
nected, 1: connected
FuncTEVnn Function type for event block nn (nn=01-06), used for IEC protocol
communication. Only present in blocks EV01-EV06.
InfoNoy Information number for event input y, y=01-16. Used for IEC protocol
communication. Only present in blocks EV01-EV06.
Parameter Range Default Unit Description
T_SUPR01 0.000-60.000
Step: 0.001
0.000 s Suppression time for event input 1 and 3.
Can only be set using the CAP 540 configu-
ration tool.
T_SUPR03 0.000-60.000
Step: 0.001
0.000 s Suppression time for event input 3 and 4.
Can only be set using the CAP 540 configu-
ration tool.
T_SUPR05 0.000-60.000
Step: 0.001
0.000 s Suppression time for event input 5 and 6.
Can only be set using the CAP 540 configu-
ration tool.
T_SUPR07 0.000-60.000
Step: 0.001
0.000 s Suppression time for event input 7 and 8.
Can only be set using the CAP 540 configu-
ration tool.
T_SUPR09 0.000-60.000
Step: 0.001
0.000 s Suppression time for event input 9 and 10.
Can only be set using the CAP 540 configu-
ration tool.