Disturbance report (DRP) Chapter 8
Monitoring
1.4 Input and output signals
Table 103: Input signals for the DISTURBREPORT (DRPn-) function blocks
Path in local HMI: ServiceReport/Functions/DisturbReport
Table 104: Output signals for the DISTURBREPORT (DRP1-) function block
1.5 Setting parameters
Path in local HMI: Settings/DisturbReport/Operation
Table 105: Parameters for disturbance report
Path in local HMI:Settings/DisturbReport/SequenceNo
Table 106: Parameters for sequence number
Path in local HMI: Settings/DisturbReport/RecordingTimes
Signal Description
CLRLEDS Clear HMI LEDs (only DRP1)
INPUT1 - INPUT48 Select binary signal to be recorded as signal no. xx were xx=1 - 48.
NAME01-48 Signal name set by user, 13 char., for disturbance presentation
FuncT01-48 Function type, set by user ( for IEC )
InfoNo01-48 Information number, set by user ( for IEC )
Signal Description
OFF Disturbance Report function turned off
RECSTART Disturbance recording started
RECMADE Disturbance recording made
MEMUSED More than 80% of recording memory used
CLEARED All disturbances in Disturbance Report cleared
Parameter Range Default Unit Description
Operation Off, On On - Determines if disturbances are recorded
(on) or not (off).
PostRetrig Off, On Off - Determines if retriggering during the post-
fault recording is allowed (on) or not (off).
Parameter Range Default Unit Description
SequenceNo 0-255
Step: 1
0 - Allows for manual setting of the sequence
number of the next disturbance.