48
Configurable logic blocks (CL1) Chapter 3
Common functions
Table 47: Output signals for the TP (TPnn-) function block
6.7.1 Setting parameters
Table 48: Setting parameters for the Pulse (TPnn-) function
6.8 Extended length pulse function block (TQ)
The function block TQ pulse timer with extended maximum pulse length, is identical with the
TP pulse timer. The difference is the longer pulse length.
Table 49: Input signals for the PULSELONG (TQnn-) function block
Path in local HMI: ServiceReport/Functions/pulseLongn
Table 50: Output signals for the PULSELONG (TQnn-) function block
6.8.1 Setting parameters
Table 51: Setting parameters for the PulseLong (TQnn-) function
Signal Description
OUT Output from pulse timer
Parameter Range Default Unit Description
T 0.000-60.000
Step:0.010
0.010 s Pulse length. Can only be set from CAP
configuration tool.
Signal Description
INPUT Input to pulse long timer
T Pulse length. See setting parameters
Signal Description
OUT Output from pulse long timer
xx00000164.vsd
TQ01-
PULSELONG
INPUT
T
OUT
Parameter Range Default Unit Description
T 0.0-90000.0
Step: 0.1
0.0 s Pulse length. Can only be set from CAP
configuration tool.