SEMOD53217-4 v13
IEC08000479 V3 EN-US
Figure 16: Transformer input module (TRM)
■ Indicates high polarity
CT/VT-input designation according to Figure 16
Current/voltage
configuration
(50/60/17.3 Hz)
AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12
12I, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A
12I, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A
10I+2U, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V
10I+2U, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V
9I+3U, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V
9I+3U, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V
5I, 1A+4I, 5A+3U 1A 1A 1A 1A 1A 5A 5A 5A 5A 110-220V 110-220V 110-220V
7I+5U, 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
7I+5U, 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V
6I, 5A+1I, 1A+5U 5A 5A 5A 5A 5A 5A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
3I, 5A+4I, 1A+5U 5A 5A 5A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
Table continues on next page
1MRK 514 026-UEN B Section 6
Connecting
670 series 2.2 IEC 43
Installation manual