MEASUREMENTS
*
Monitored measured values
*
RECORDED DATA
*
Stored event values from the protection functions
*
Registered number of pickups of protection functions
*
Continuously updated registers of actual values from protection functions
*
INFO
*
Information on the relay, such as device type and relay serial number
4.2.1.2. How to monitor measured values
You can monitor all measured values via MEASUREMENTS in the HMI menu. In
addition, the measured current values on phases I
a
,I
b
and I
c
and the measured value
of I
n
can also be monitored by activating the monitoring state.
To access the measured values on phases I
a
,I
b
and I
c
and the measured value of I
n
,
TH LEVEL via the HMI menu:
1. Press an arrow button to access the main menu.
2. The cursor is at the first menu item, MEASUREMENTS. Press to see the
measured value on phase I
a
.
3. Use
and to monitor the measured values on phases I
a
,I
b
and I
c
and the
measured value of I
n
,I
2
and TH LEVEL. The phase currents and the value of I
2
are shown as multiples of the rated current, which correspond to the full load
current (FLC) of the motor. I
n
is shown as a percentage of the rated current of the
current transformer (CT) while TH LEVEL is shown as a percentage of the
thermal trip level. Press
once more to see the corresponding primary current
value for I
a
,I
b
,I
c
and I
n
. If the conversion factors are set to zero, dashes "---"
are displayed instead.
4. Use the arrow buttons to monitor other measured values in the menu DEMAND
VALUES; see Fig. 4.2.1.2.-1.
5. Press
to return the display to the idle mode.
26
REM 610REM 610
Motor Protection Relay
Operator's Manual - ANSI ve rsion
1MRS755538