Disabled Quantity not selected
U23 Phase-to-phase 23 voltage
U31 Phase-to-phase 31 voltage
UL1 Phase-to-earth 1 voltage
UL2 Phase-to-earth 2 voltage
UL3 Phase-to-earth 3 voltage
U12B Phase-to-phase 12 voltage, B side
U23B Phase-to-phase 23 voltage, B side
U31B Phase-to-phase 31 voltage, B side
UL1B Phase-to-earth 1 voltage, B side
UL2B Phase-to-earth 2 voltage, B side
UL3B Phase-to-earth 3 voltage, B side
S Apparent power
P Real power
Q Reactive power
PF Power factor
If the data source for the selected quantity is removed, for example, with
Application Configuration in PCM600, the load profile recorder stops
recording it and the previously collected data are cleared.
3.19.2.2 Length of record
The recording capability is about 7.4 years when one quantity is recorded and
the demand interval is set to 180 minutes. The recording time scales down
proportionally when a shorter demand time is selected or more quantities are
recorded. The recording lengths in days with different settings used are presented
in
Table 212
. When the recording buffer is fully occupied, the oldest data are
overwritten by the newest data.
Table 212: Recording capability in days with different settings
Demand interval
1 5 10 15 30 60 180
Table continues on the next page
Basic functions 1MRS758755 C
192 REC615 & RER615
Technical Manual