PEMMXU Input signals
Table 629: PEMMXU Input signals
Name Type Default Description
I_A SIGNAL 0 Phase A current
I_B SIGNAL 0 Phase B current
I_C SIGNAL 0 Phase C current
U_A SIGNAL 0 Phase A voltage
U_B SIGNAL 0 Phase B voltage
U_C SIGNAL 0 Phase C voltage
RSTACM BOOLEAN 0=False Reset of accumulated
energy reading
8.1.11.4 Settings
PEMMXU Non group settings
Table 630: PEMMXU Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Power unit Mult
3=Kilo
6=Mega
3=Kilo Unit multiplier for
presentation of the
power related val-
ues
Energy unit Mult
3=Kilo
6=Mega
3=Kilo Unit multiplier for
presentation of the
energy related val-
ues
Active power Dir
1=Forward
2=Reverse
1=Forward Direction of active
power flow: For-
ward, Reverse
Reactive power Dir
1=Forward
2=Reverse
1=Forward Direction of reac-
tive power flow:
Forward, Reverse
Table 631: PEMMXU Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Forward Wh Initial 0...999999999 1 0 Preset Initial value for for-
ward active energy
Reverse Wh Initial 0...999999999 1 0 Preset Initial value for re-
verse active energy
Forward VArh Initial 0...999999999 1 0 Preset Initial value for for-
ward reactive energy
Reverse VArh Initial 0...999999999 1 0 Preset Initial value for re-
verse reactive energy
Measurement mode
1=PhsA, PhsB, PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
1=PhsA, PhsB, PhsC Selected measurement
mode for power calcula-
tion
1MRS758755 C Measurement functions
REC615 & RER615
Technical Manual
603