Parameter Values (Range) Unit Step Default Description
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
8.1.11.5 Monitored data
PEMMXU Monitored data
Table 632: PEMMXU Monitored data
Name Type Values (Range) Unit Description
S-kVA FLOAT32 -999999.9...9999
99.9
kVA Total Apparent
Power
P-kW FLOAT32 -999999.9...9999
99.9
kW Total Active Pow-
er
Q-kVAr FLOAT32 -999999.9...9999
99.9
kVAr Total Reactive
Power
PF FLOAT32 -1.00...1.00 Average Power
factor
RSTACM BOOLEAN
0=False
1=True
Reset of accu-
mulated energy
reading
S_INST FLOAT32 -999999.9...9999
99.9
kVA Apparent power,
magnitude of in-
stantaneous val-
ue
S_DB FLOAT32 -999999.9...9999
99.9
kVA Apparent power,
magnitude of re-
ported value
S_DMD FLOAT32 -999999.9...9999
99.9
kVA Demand value of
apparent power
P_INST FLOAT32 -999999.9...9999
99.9
kW Active power,
magnitude of in-
stantaneous val-
ue
P_DB FLOAT32 -999999.9...9999
99.9
kW Active power,
magnitude of re-
ported value
P_DMD FLOAT32 -999999.9...9999
99.9
kW Demand value of
active power
Q_INST FLOAT32 -999999.9...9999
99.9
kVAr Reactive power,
magnitude of in-
stantaneous val-
ue
Table continues on the next page
Measurement functions 1MRS758755 C
604 REC615 & RER615
Technical Manual