ABB | SACE Emax 2
Ekip Dip protection release | 4 - Test
45 | © 2014 ABB | 1SDH000999R0002 - L8569
4 - Test
Presentation
The Ekip TT, Ekip T&P and Ekip Bluetooth modules connected to the Ekip Dip release allow you to perform
various tests:
• Release LED test
• Check on the presence of the internal battery.
• Circuit-breaker opening test (trip test).
• Protection test
LED test
The LED test can be performed directly on Ekip Dip:
Phase Operation
1 Connect a module to the front test connector of frontal test.
2 Press the iTest push-button for at least 6 seconds, but less than 9 seconds.
3 When the protection LEDs light up, release the iTest push-button.
4
Check the following switch-on sequence:
•S,I,GLEDsonxed.
•LedprealarmLandalarmLthatalternatethreetimes.
•AlltheprotectionLEDsoff
Battery test
The battery check is integrated in the LED test procedure, except for the battery error signal:
• If the battery is absent or not working, after iTest is pressed the error is signalled by five flashes of the
prealarm led L.
• If the battery is present and working, the LED test proceeds as in the normal procedure.
Protection test
In order to perform the protection test, follow the instructions below:
Phase Operation
1 Make sure that the circuit-breaker is closed and that there are no primary currents.
2 Connect Ekip T&P or Ekip Bluetooth to the front test connector.
3 Start the communication with Ekip Connect.
4
Open the Information page and select the Test command, which opens the protection test
page.
5 Set up the test as required and verify that the release functions properly.
Further information on Ekip Connect is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the manual 1SDH000891R0002.
Opening test
The opening test can be performed directly on the release or from Ekip Connect.
To perform the release test:
Phase Operation
1 Make sure that the circuit-breaker is closed and that there are no primary currents.
2 Connect a module to the front test connector of frontal test.
3 Press the iTest push-button for at least 9 seconds.
4 Check that the circuit-breaker opens and that the TU Reset button comes out
To perform the test from Ekip Connect:
Phase Operation
1 Make sure that the circuit-breaker is closed and that there are no primary currents.
2 Connect Ekip T&P or Ekip Bluetooth to the front test connector.
3 Start the communication with Ekip Connect.
4 Select the trip test command.
5 Check that the circuit-breaker opens and that the TU Reset button comes out
Further information on Ekip Connect is available from the web site http://www.abb.com/abblibrary/