Ekip DIP default parameters
The Ekip Dip releases are supplied with the following default parameters, some adjustable with the front dip-
switch (protections, Frequency, Neutral), other via front bus.
Protection/Parameter Value
L 1 In; 144 s
S
(1)
Off; 0.1 s
I 4 In
G
(1)
Off; 0.1 s
Frequency 50 Hz (IEC) / 60 Hz (UL)
Neutral
Off (for circuit breakers three-pole).
50 % (for four-pole circuit-breaker)
Hardware Trip Disabled
Measurement interval 5 minutes
Local Bus Disabled
Alive LED Disabled (Power LED on fixed)
(1)
Protection S available with LSI and LSIG versions of the release. Protection G available with LSIG version.